Fire Extinguisher Identification

Fire extinguisher2 Fire Extinguisher IdentificationFire Extinguisher Identification to BS EN3 and BS 7863

Under BS EN 3 operative from the 1st January 1997, all new certified fire extinguishers used in European Union countries must feature red bodies. In line with familiar UK practice, BS 7863 allows manufacturers to affix coloured identification panels on or above the operating instructions covering no more than 5% of the body surface area and visible through a horizontal arc of 180 degrees when the extinguisher is mounted.  

The new harmonised European standard on fire extinguishers – BS EN3 –  which came into effect in 1st January 1997, provides a single standard for fire extinguishers across Europe. It replaced the old British Standard BS 5423, which has now been withdrawn.  

BS EN3 is the standard now used for the specification, manufacturing and purchase of extinguishers in the UK. An additional standard BS 7863 details the revised colour coding system and supplements BS EN3.  

BS EN3 is not retrospective and pre-existing extinguishers do not need to be replaced with extinguishers to this new standard. However, any replacements as a result of damageFire extinguisher Fire Extinguisher Identification, wear or un-serviceability or new extinguishers will need to meet this new, later standard.While BSEN3 has now been in place for a number of years Understanding the colours and codes should be part of your regular health and safety training and form part of your new staff induction programme. There are a number of resources such as Fire Extinguisher Colour Guide Code Charts and Fire Extinguisher colour code guide pocket guides that can serve as staff information points and training aids. Fire Extinguisher location panels can aid your routine premises maintenance. As well as providing information on the use of the particular fire extinguisher mounted they also give a visual warning as to when the extinguisher has been used and not replaced. 

The New Standard Fire Extinguisher Standard
The main differences between the old and new standards are:

  • A minimum of 95% of the extinguisher body must be red
  • Zones of colour, indicating the contents of the extinguisher, are permitted
  • The markings on the extinguisher must follow a specified layout
  • Pictograms are used indicating the type of fires that the extinguisher is suitable for
  • A minimum body shell thickness is specified
  • Minimum fire performance ratings for the size of the extinguisher are specified
  • Operating temperatures of some extinguishers are increased
  • Some discharge times are increased

Although there are many technical changes and the improvements in the new standard, the most noticeable change is to the colour of the extinguisher bodies.  

1988 Fire Extinguisher Identification

Fire Extinguisher Colour Guide Code

Fire Extinguisher Colours and Codes

Understanding the colours and codes should be part of your regular health and safety training and form part of your new staff induction programme. There are a number of resources such as Fire Extinguisher Colour Guide Code Charts and Fire Extinguisher colour code guide pocket guides that can serve as staff information points and training aids. In the UK we were used to a system of using the colour of the body of the extinguisher to indicate its contents. However, this system has been peculiarly British with all extinguishers in Europe being coloured completely red.  

Since extinguisher colour is no longer used to identify the type of the extinguisher, it falls to the standard pictograms to illustrate the types of fire that extinguisher can be used on. The pictograms are: kbase fireextinguisher pictogram Fire Extinguisher Identification  

Class A fires involving organic solids; e.g. wood, paper
Class B fires involving flammable liquids
Class C fires involving flammable gases
Class F fires involving cooking oil and fat  

A concession was made in this latest standard for a small zone of colour to be available on the body of the extinguisher to further help identify the contents of the extinguisher. A colour zone of up to 5% of the surface area of the extinguisher can be positioned on the top half of the front of the extinguisher body and be visible from 180 degrees. The British Standard BS 7863 outlines the colours that can be used in this way and follows the colour coding that has been used for many years. In addition, there is now a new colour for the Wet Chemical extinguisher (see guide above). The colour codes are:  

Red – Water
Cream – Foam
Blue – Powder
Black – Carbon Dioxide
Canary Yellow – Wet Chemical  

A further effect of the latest standard is that customised colours (most commonly chromed stainless steel) are no longer allowed; although, as there is no immediate need to change these extinguishers, they (and particularly the stainless extinguishers) may well be in use for some considerable time.  

  

Replacement of Extinguishers
Even though pre-existing extinguishers do not need to be replaced, the gradual appearance of the new, latest standard extinguishers alongside older types may cause some confusion. The continued presence of other coloured extinguishers in an area may suggest to some users that the red extinguishers will contain water but this might not be the case, with potentially serious consequences.  

Everyone should now what to do in the event of a fire and this includes being able to select the appropriate type of extinguisher to use. To reduce the chances of confusion, mixing new and old standard extinguishers in the same area or building should be avoided.  

Note also that the British Standard on servicing BS5306: Part 4 states that all extinguishers installed in any one building or single occupancy should have the same method of operation and, if intended for the same function, should all be similar in shape, appearance and colour.  

Summary for Fire Extinguisher Identification

  • Ensure that all new extinguishers obtained comply with BS EN3
  • Ensure that everyone is able to identify the different types of fire extinguisher and their respective use through training & Guides
  • Provide information on the colour standards for fire extinguishers
  • Clearly sign extinguishers and their use with fire safety equipment signs
  • Do not mix extinguishers conforming to the old and new standards
  • Do not mix extinguishers which have different operating methods

Stocksigns has the largest range of fire fighting equipment signs on the market for more information on these and our other safety signs why not order our safety signs catalogue or call our Sales Team on 01737 774077.

Where to use Electrical Emergency Luminaires

Door lighting Where to use Electrical Emergency LuminairesElectrical Emergency Luminaires – Joanna Godden

Emergency lighting is designed to illuminate automatically the emergency escape route (i.e. staircases, landings, passageways etc.) upon failure of the supply to the normal artificial lighting. The emergency lighting must comply with BS 5266: 2005. It is vital that emergency lighting comes on if the normal lighting fails. It needs to be sufficiently bright, illuminated for enough time, and the light sources so positioned that the staff and visitors of a building can be evacuated safely in an emergency

Siting of Luminaires

Luminaires should be sited in the following positions:

  • At each exit door
  • At each intersection of corridors
  • At each change of direction
  • Close to each staircase
  • Close to any change in floor level
  • Close to fire equipment and alarm call point locations
  • At locations that adequately illuminate emergency escape and safety signs

Maintained & Non-maintained Systems.

Non-maintained systems are used in buildings with a limited occupation time, such as offices and shops, and only operate when the power fails. In general, Maintained systems are required for places of entertainment and licensed premises and can be on all the time from normal mains supply, remaining on when the power fails.

emergency luminaire Finishes Available Where to use Electrical Emergency Luminaires

For more information contact our sales team on Tel 01737 774077 or sales@stocksigns.co.uk00393 ceiling mounted emergency luminaire7010 Where to use Electrical Emergency Luminaires00392 wall mounted emergency luminaire 7010 Where to use Electrical Emergency Luminaires

Top 10 signage areas to consider for the Disability Discrimination Act

03625 cut out1 224x300 Top 10 signage areas to consider for the Disability Discrimination Act

Safety signs and Disability Discrimination Act

On October 1st 2004 the final stage of the goods, facilities and services provisions part 3 of the Disability Discrimination Act came into force. Although the legislation has been in place for some time our need to meet the guidelines is still firmly in place. This article is a reminder of what we need to consider in terms of signs and our obligations to the DDA.

The aim of this legislation is to achieve equality between the disabled and able-bodied; it introduces a basic duty not to treat disabled people less favourably than others. The new basic duty or obligations apply to anyone providing a paid or unpaid service to the public. As a “service provider” you must ensure that access is available to all disabled people and that entry routes, facilities and all information are clearly defined and indicated by suitable signage. The regulations concern access, mobility and site signage, they apply to all service providers, ranging from large corporations to small businesses (not the owners of the premises).

Under recent changes to part 2 of the Act, all employers must now ensure that they do not discriminate against disabled people in terms of recruitment and employment conditions. Compliance with the DDA can be achieved effectively by most businesses within a modest budget; however, planning is essential to ensure that the disabled user is not at a disadvantage. The new provisions are a further important step towards ensuring that disabled people have access to services that others take for granted.

10 Sign areas to consider with the Disability Discrimination Act

 

You are required to make reasonable adjustments to your premises; the areas to be considered are the signing and marking of:

  1. designating car parking bays
  2. setting down points
  3. routes to and around buildings
  4. building entrances and exits
  5. directions to facilities i.e. lifts, stairs, reception, toilets, restaurants etc.
  6. information on additional services available to the disabled
  7. clear indication of help points
  8. emergency exit routes
  9. emergency disabled refuges
  10. the enhancement of general information signage

For additional advice on signage and the DDA we would recommend carrying out a site survey for your premises.

ISO 7010 – An Overview

7010 HARD HATS1 ISO 7010 – An OverviewISO 7010 – An Introduction

Over the next few months we will see the adoption of a new standard for safety signs as ISO 7010 is soon to become Pr EN 7010. The change will see safety signs in the workplace move away from being an “International standard” (essentially a recommendation on best practice), to a European norm (meaning the contents of the standard must be written into UK and EU law). ISO 7010 has been developed to provide consistency in design across the EU. We will be phasing in the new designs throughout 2011 and you may notice some design changes to the symbols whereas others will look virtually unchanged. Whilst the new symbols will be replacing the old designs, both designs will still meet your safety obligations.

ISO 7010 – An Overview.

In the late seventies, as the European Community was coming into being, it was recognised that with a large migratory workforce within the EU countries, there would be a real problem communicating health and safety issues.

It was decided to create an international standard based on pictograms. This lead to the publishing, in 1984, of the first health and safety standard; ISO 3864-Safety Colours and Safety Signs, which is still current today and is the basis for both ISO 7010 and BS 5499.

Because ISO 3864 was not grounded in law, it did not become established across the EU. So, in 1992, a European Directive based on ISO 3864 was passed, which made it a legal requirement for member states to write the requirements into their countries health and safety legislation, this was EC Directive 92/58/EEC.
In the UK this took the form of the “Health & Safety (Signs and Signals) Regulations 1996.

The Directive was a bit vague regarding the symbols to be used and soon a variety of different symbols had developed across Europe, the “Euro” fire exit symbol being a good example.

The situation regarding these symbols now needed to be rectified.

Here in Britain, this lead to the revision of the previous standard and in 2002, BS5499:2002 Graphical Symbols and Signs, was issued.

The need for correct pictograms across Europe was now evident and so the International Standards Organisation were compelled to update their own standards and so, using BS 5499 as a basis, they split ISO 3864 into two parts:

ISO 3864:2002 – covering shape and colours, as before.
ISO 7010:2003 – covering pictograms.

As previously seen in the Eighties, for these changes to have any impact, it would be necessary to write this standard into law, which is the process we are in the middle of now.

Making ISO 7010 into an EN, means that the status of the standard will change from being a recommendation of best practice, to a European Norm, requiring that the contents of the Standard are written, without change, into all EU countries laws.

This means that there will be a legal requirement for the same sign to be used in every country for the same requirement.
It will mean that a fire exit sign in England will be the same as it would be in France, Spain, Germany or anywhere at all within the EU.

ISO 7010 – A Brief History – milestone timeline

Late seventies – large migratory workforce in the EEC
1978 – BS 5499 – Fire Safety Signs, Notices and Graphic Symbols
1992 – EC Directive 92/58/EEC
1996 – “The Health & Safety (Signs and Signals) Regulations
2002 – BS 5499:2002 – Graphical Symbols and Signs
2003 – ISO 3864:2002 and ISO 7010:20037010 NO SMOKING ISO 7010 – An Overview

our new 2011 catalogue is has been completely updated to include the NEW ISO 7010 safety symbols